Power Supplies

Power Supply – Each rack in the system requires its own power supply. There are many power supply options to accommodate any configuration. The power supply mounts in the left, unnumbered slot of each rack. There are 2 main categories of power supplies used in the 90-30 system: the AC/DC Input Power Supplies and the DC Input Only Power Supplies. All of these have 30 watts total output. The AC/DC models come in standard and high capacity models. The DC Only models feature 24/48 VDC input, 48 VDC input, and high capacity 24 VDC input.

PART
NUMBER
LOAD
CAPACITY
NOMINAL
INPUT
OUTPUT CAPACITIES
VOLTAGE/POWER (TOTAL CANNOT EXCEED 30 WATTS)
IC693PWR32130 WATTS100 to 240 VAC or
125 VDC
+ 5 VDC
15 WATTS
+ 24 VDC ISOLATED
20 WATTS
+ 24 VDC RELAY
15 WATTS
IC693PWR33030 WATTS100 to 240 VAC or
125 VDC
+ 5 VDC
30 WATTS
+ 24 VDC ISOLATED
20 WATTS
+ 24 VDC RELAY
15 WATTS
IC693PWR32230 WATTS24 or 48 VDC+ 5 VDC
15 WATTS
+ 24 VDC ISOLATED
20 WATTS
+ 24 VDC RELAY
15 WATTS
IC693PWR32830 WATTS48 VDC+ 5 VDC
15 WATTS
+ 24 VDC ISOLATED
20 WATTS
+ 24 VDC RELAY
15 WATTS
IC693PWR33130 WATTS24 VDC+ 5 VDC
30 WATTS
+ 24 VDC ISOLATED
20 WATTS
+ 24 VDC RELAY
15 WATTS